BS 6622 Three Core Armoured 11kV XLPE Stranded Aluminium Conductors
Construction
| cross-sectional area mmsq  | Minimum average thickness of insulation mm  | Nominal
      diameter over insulation 
 | Nominal thickness of PVC bedding mm | Nominal number and diameter of armoured wires no./mm | Nominal thickness of PVC oversheath mm | Nominal overall diameter of cable mm  | 
| 70 | 3.4 | 18.8 | 1.4 | 54/2.5 | 2.7 | 57.1 | 
| 95 | 3.4 | 20.5 | 1.5 | 59/2.5 | 2.8 | 61.2 | 
| 120 | 3.4 | 22.0 | 1.6 | 62/2.5 | 3.0 | 65.0 | 
| 150 | 3.4 | 23.3 | 1.6 | 65/2.5 | 3.1 | 68.0 | 
| 185 | 3.4 | 25.1 | 1.7 | 70/2.5 | 3.2 | 72.3 | 
| 240 | 3.4 | 27.3 | 1.8 | 61/3.15 | 3.4 | 79.0 | 
| 300 | 3.4 | 29.6 | 1.9 | 65/3.15 | 3.6 | 84.5 | 
| 400 | 3.4 | 32.3 | 2.0 | 70/3.15 | 3.8 | 90.9 | 
Installation
| cross-sectional area mmsq  | Approximate cable weight kg/m | Nominal drum length  m | Minimum bending radius mm  | Nominal  internal diameter of ducts mm  | 
| 70 | 5.1 | 500 | 700 | 100 | 
| 95 | 5.7 | 500 | 750 | 100 | 
| 120 | 6.4 | 500 | 800 | 100 | 
| 150 | 6.9 | 500 | 850 | 125 | 
| 185 | 7.3 | 500 | 900 | 125 | 
| 240 | 9.7 | 500 | 950 | 125 | 
| 300 | 10.9 | 450 | 1050 | 125 | 
| 400 | 12.5 | 400 | 1100 | 125 | 
Electrical Performance
| cross-sectional area mmsq  | Maximum DC resistance of conductor at 20 
    
     ℃
    
uohms/m  | Maximum AC resistance of conductor at 90 ℃ uohms/m  | Reactance at 50Hz  uohms/m | Impedance at 50Hz uohms/m  | Maximum Capacitace PF/m  | Maximum charging current at normal voltage and frequency mA/m  | 
| 70 | 443 | 568 | 108 | 578 | 298 | 0.62 | 
| 95 | 320 | 410 | 102 | 422 | 334 | 0.67 | 
| 120 | 253 | 325 | 98.8 | 340 | 365 | 0.73 | 
| 150 | 206 | 265 | 96.2 | 282 | 392 | 0.78 | 
| 185 | 164 | 211 | 93.1 | 231 | 430 | 0.86 | 
| 240 | 125 | 161 | 90.0 | 184 | 476 | 0.95 | 
| 300 | 100 | 130 | 87.4 | 157 | 524 | 1.05 | 
| 400 | 77.8 | 102 | 84.9 | 133 | 580 | 1.16 | 
Ratings
| Cross-sectional area  mmsq | Current Ratings  | Short circuit ratings  | |||
| Laid direct in ground Amps | Drawn into ducts Amps | Laid in air Amps | One second short circuit rating of conductor KA | One second short circuit rating of copper per core KA | |
| 70 | 195 | 165 | 210 | 6.3 | Typically less than 1kA | 
| 95 | 230 | 200 | 250 | 8.5 | |
| 120 | 265 | 225 | 295 | 11.0 | |
| 150 | 295 | 255 | 330 | 13.5 | |
| 185 | 335 | 290 | 385 | 17.0 | |
| 240 | 380 | 335 | 450 | 22.3 | |
| 300 | 435 | 375 | 510 | 28.0 | |
| 400 | 480 | 420 | 570 | 36.6 | |